Coding level 1
"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" group
Coding in the delivered condition
Party mode time limit
F2:8
Time limit for party mode or exter-
nal operating program changeover
via pushbutton: 8 h
Note
Observe settings of coding ad-
dresses "3A", "3b", "3C" in the
"General" group and "d5" and
"d8" in the "Heating circuit..."
group.
Start temperature raising
F8:–5
Outside temperature limit for rais-
ing the reduced set room tempera-
ture
page 80
Observe the setting of coding ad-
dress "A3".
End temperature raising
F9:–14
Outside temperature limit for rais-
ing the reduced set room tempera-
ture to the standard set room tem-
perature
page 80
Set flow temperature increase
FA:20
Raising of the set boiler water/flow
temperature by 20 % when chang-
ing from operation with reduced
room temperature to operation with
standard room temperature. See
example on page 80.
Duration set flow temperature increase
Fb:30
Time period for raising the set boil-
er water temperature/flow temper-
ature (see coding address "FA")
60 min. See example on
page 80.
In the "Heating and DHW" operating program, party mode ends automatically when the system changes over to operation
*1
with standard room temperature.
40
*1
5 °C, see example on
14 °C, see example on
Possible change
F2:0
No time limit
F2:1
Time limit adjustable from 1 to 12 h
to
F2:12
F8:+10
Outside temperature limit adjustable
to
from +10 to
F8:–60
F8:–61
Function disabled
F9:+10
Outside temperature limit adjustable
to
from +10 to
F9:–60
FA:0
Temperature rise adjustable from 0
to
to 50 %.
FA:50
Fb:0
Time period adjustable from 0 to
to
300 min.
Fb:150
1 step
(cont.)
*1
60 °C.
60 °C
2 min
*1