Vitotronic 300, GW5B Installation and Service
"Solar" Group
(continued)
Only in conjunction with solar control module, type SM1.
Coding in the delivered condition
Extended solar control functions
20:0
No extended control function enabled.
"Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group
Coding in the delivered condition
Priority DHW heating
A2:2
DHW tank priority for heating circuit pump and
mixing valve.
Economy function outside temperature
A5:5
With heating circuit pump logic function
(economy mode): heating circuit pump "OFF"
when the outside temperature (AT) is 1 K
higher than the set room temperature (RTset)
AT > RTset + 1 K
Parameter address
A5:...
1
2
3
4
5
6
7
to
15
With heating circuit pump logic function: Heating circuit pump "OFF"
AT > RTset + 5 K
AT > RTset + 4 K
AT > RTset + 3 K
AT > RTset + 2 K
AT > RTset + 1 K
AT > RTset
AT > RTset – 1 K
AT > RTset – 9 K
Possible change
20:1
Additional function for DHW heating.
20:2
Differential temperature control 2.
20:3
Differential temperature control 2 and auxiliary
function.
20:4
Differential temperature control 2 for central
heating backup.
20:5
Thermostat function.
20:6
Thermostat function and auxiliary function.
20:7
Solar heating via external heat exchanger without
additional temperature sensor.
20:8
Solar heating via external heat exchanger with
additional temperature sensor.
20:9
Solar heating of two DHW tanks.
Possible change
A2:0
Without DHW tank priority applicable
to heating circuit pump and mixing valve.
A2:1
DHW tank priority applies only to mixing valves.
A2:3
Modulating priority applies to mixing valves,
to
i.e. the heating circuit receives a reduced
A2:15
amount of heat.
A5:0
Without heating circuit pump logic function.
A5:1
With heating circuit pump logic function: Heating
to
circuit pump "OFF"; see the following table.
A5:15
Code 1
59