Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 53

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" group
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C4:1
Do not adjust
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only when operat-
ing with standard room tempera-
ture)
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
d3:14
Heating curve slope: 1.4.
d4:0
Heating curve level: 0
d5:0
With external heating program
changeover (observe setting for
coding addresses "3A", "3b" and
"3C" in the "General" group):
Heating program switches to "Con-
stant central heating with reduced
room temperature" or "Standby
mode" (subject to the setting of the
set reduced room temperature).
d6:0
Heating circuit pump at signal "Ex-
ternal blocking":
Control mode
(Observe settings of coding ad-
dresses "3A", "3b" and "3C" in the
"General" group).
d7:0
Heating circuit pump at signal "Ex-
ternal demand":
Control mode
(Observe settings of coding ad-
dresses "3A", "3b" and "3C" in the
"General" group).
d8:0
With EA1 extension:
No heating program changeover
E1:1
With remote control:
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
1 K
>
actual
set
RT
2 K
>
actual
set
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters).
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters).
d3:2
Heating curve slope adjustable from
to
0.2 to 3.5
d3:35
d4:–13
Heating curve level adjustable from
to
13 to 40
d4:40
d5:1
Heating program switches to "Con-
stant operation with standard room
temperature".
d6:1
"Off"
d6:2
"On"
d7:1
"Off"
d7:2
"On"
d8:1
Heating program changeover via in-
put DE1
d8:2
Heating program changeover via in-
put DE2
d8:3
Heating program changeover via in-
put DE3
E1:0
Set day temperature adjustable from
3 to 23 °C
Coding level 2
(cont.)
+ 2 K
+ 1 K
1 K
2 K
3 K
53