Solar" Group; Coding - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

"DHW" group
(cont.)
Coding in the delivered condition
59:0
Cylinder heating:
Start point
Stop point +2.5 K
5b:0
Do not adjust
5E:0
Circulation pump for cylinder heat-
ing at "External blocking" signal:
Control mode
5F:0
Circulation pump for cylinder heat-
ing at signal "External demand":
Control mode
60:20
During DHW heating, the boiler
water temperature is up to 20 K
higher than the set DHW tempera-
ture.
61:0
The circulation pump for cylinder
heating is started subject to boiler
water temperature.
62:10
Circulation pump with max 10 min
run-on time after cylinder heating
67:40
For solar DHW heating:
Set DHW temperature 40 °C. Re-
heating is suppressed above the
selected set temperature (DHW
heating blocked by the boiler).
71:0
DHW circulation pump:
"ON" according to time program
72:0
DHW circulation pump:
"ON" according to time program
73:0
DHW circulation pump:
"ON" according to time program

"Solar" group

Only in conjunction with solar control module, type
SM1

Coding

Coding in the delivered condition
00:8
Start temperature differential for
solar circuit pump 8 K
2.5 K
Possible change
59:1
Start point adjustable from 1 to 10 K
to
below set value.
59:10
5E:1
"Off"
5E:2
"On"
5F:1
"Off"
5F:2
"On"
60:5
The differential between the boiler
to
water temperature and the set DHW
60:50
temperature is adjustable from 5 to
50 K.
61:1
The circulation pump for cylinder
heating starts immediately.
62:0
No circulation pump run-on
62:1
Run-on time adjustable from 1 to
to
15 min
62:15
67:0
Set DHW temperature adjustable
to
from 0 to 90 °C (limited by boiler-
67:90
specific parameters).
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:1
"OFF" during DHW heating to set
value 2
72:2
"ON" during DHW heating to set val-
ue 2
73:1
During the time program "ON" 1 to 6
to
times/h for 5 min
73:6
73:7
Constantly "ON"
Possible change
00:2
Start temperature differential adjust-
to
able from 2 to 30 K
Coding level 2
47

Hide quick links: