Coding - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

"General" group

Coding

Coding in the delivered condition
00:1
One heating circuit without mixer
A1 (heating circuit 1), without
DHW heating
Value address
Description
00: ...
2
1 heating circuit without mixer A1 (heating circuit 1),
with DHW heating, is recognised automatically.
3
1 heating circuit with mixer M2 (heating circuit 2),
without DHW heating
4
1 heating circuit with mixer M2 (heating circuit 2),
with DHW heating
5
1 heating circuit without mixer A1 (heating circuit 1),
one heating circuit with mixer M2 (heating circuit 2),
without DHW heating, is recognised automatically.
6
1 heating circuit without mixer A1 (heating circuit 1),
one heating circuit with mixer M2 (heating circuit 2),
with DHW heating, is recognised automatically.
7
2 heating circuits with mixer M2 (heating circuit 2) and M3 (heating circuit 3),
without DHW heating
8
2 heating circuits with mixer M2 (heating circuit 2) and M3 (heating circuit 3),
with DHW heating
9
1 heating circuit without mixer A1 (heating circuit 1),
2 heating circuits with mixer M2 (heating circuit 2) and M3 (heating circuit 3),
without DHW heating, is recognised automatically.
10
1 heating circuit without mixer A1 (heating circuit 1),
2 heating circuits with mixer M2 (heating circuit 2) and M3 (heating circuit 3),
with DHW heating, is recognised automatically.
Coding in the delivered condition
1E:0
With EA1 extension (analogue in-
put 0
Temperature demand from 0 to
100 °C:
1 V
10 V
2E:0
Without wireless outside tempera-
ture sensor
32:0
Do not adjust
33:0
Do not adjust
34:0
Do not adjust
35:0
Without EA1 extension
36:0
Function output
sion:
Fault message
3b:0
Function input DE2 at EA1 exten-
sion:
No function
10 V):
10 °C
100 °C
aBJ
at EA1 exten-
Possible change
00:2
For system schemes, see the follow-
to
ing table
00:10
Possible change
1E:1
Temperature demand from 30 to
120 °C:
1 V
10 V
2E:1
With wireless outside temperature
sensor; automatic recognition.
2E:2
Wireless outside temperature sensor
not used.
35:1
With EA1 extension; automatic rec-
ognition.
36:1
Do not adjust
36:2
Do not adjust
3b:1
Heating program - changeover
Coding level 2
30 °C
120 °C
41