Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 66

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Troubleshooting
Faults that are not displayed at the...
Heating circuit pump not running
Is plug
'live' between L and N?
No
Check fuse F1, 6.3 A (slow). If the fuse has blown:
1. Pull plug
.
2. Replace the F1 fuse.
3. Repeat this test if fuse F1 remains intact but the pump
connection does not go 'live'. Possibly replace the main
PCB.
66
(cont.)
Yes
1. Check pump connection and pump.
2. Check any further switching devices that may be
installed (e.g. maximum temperature controller).