Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 38

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Coding level 1
"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" group
Parameter address A5:...
6
7
to
15
Coding in the delivered condition
Extended economy function, adjusted outside temperature
A6:36
Extended economy mode disa-
bled.
Extended economy function, mixer
A7:0
Only for heating circuits with mixer:
Without mixer economy function
Pump idle time, transition reduced mode
A9:7
With pump idle time (heating circuit
pump "OFF", see function descrip-
tion, page 78)
Note
The max. idle period is 10 h.
Weather-compensated/room temperature hook-up
b0:0
With remote control:
Heating mode/reduced mode:
Weather-compensated (change
code only for heating circuits with
mixer)
Economy function, room temperature
b5:0
With remote control: No room tem-
perature-dependent heating circuit
pump logic function (change code
only for heating circuits with mixer)
38
With heating circuit pump logic function: Heating circuit pump "OFF"
OT
RT
>
set
OT
RT
1 K
>
set
OT
RT
9 K
>
set
Possible change
A6:5
to
A6:35
A7:1
A9:0
A9:1
to
A9:15
b0:1
b0:2
b0:3
b5:1
to
b5:8
(cont.)
Extended economy mode enabled,
i.e. at a variably adjustable value be-
tween 5 and 35 °C plus 1 °C, the
burner and heating circuit pump will
stop and the mixer will close. The
basis for this is the adjusted outside
temperature. The adjusted outside
temperature is based on the actual
outside temperature and a time con-
stant, which takes the cooling down
of an average building into consider-
ation.
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
If the mixer has been trying to
close for longer than 20 min.
Heating circuit pump "ON":
If the mixer changes to control
function.
If there is a risk of frost
Without pump idle time
With pump idle time, adjustable from
1 to 15:
1 = short idle time
15 = long idle time
Heating mode: Weather-compensa-
ted
Reduced mode: With room tempera-
ture hook-up
Heating mode: With room tempera-
ture hook-up
Reduced mode: Weather-compen-
sated
Heating mode/reduced mode: With
room temperature hook-up
For heating circuit pump logic func-
tion, see the following table