Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 54

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Coding level 2
"Heating circuit 1", "Heating circuit 2", "Heating circuit 3" group
Coding in the delivered condition
Set day value adjustable at the re-
mote control from 10 to 30 °C
E2:50
With remote control:
No display correction of the actual
room temperature
F1:0
Screed drying disabled
F2:8
Time limit for party mode or exter-
nal operating program changeover
via pushbutton: 8 h
Note
Observe settings of coding ad-
dresses "3A", "3B", "3C" in the
"General" group and "d5" and
"d8" in the "Heating circuit..."
group.
F8:–5
Outside temperature limit for rais-
ing the reduced set room tempera-
ture
page 80
Observe the setting of coding ad-
dress "A3".
F9:–14
Outside temperature limit for rais-
ing the reduced set room tempera-
ture to the standard set room tem-
perature
page 80
FA:20
Raising of the set boiler water or
flow temperature by 20 % when
changing from operation with re-
duced room temperature to opera-
tion with standard room tempera-
ture. See example on page 80.
Fb:60
Time period for raising the set boil-
er water or set flow temperature
(see coding address "FA") 60 min.
See example on page 80.
In the "Heating and DHW" operating program, party mode ends automatically when the system changes over to operation
*1
with standard room temperature.
54
*1
5 °C, see example on
14 °C, see example on
Possible change
E1:2
Set day temperature adjustable from
17 to 37 °C
E2:0
Display correction
to
to
E2:49
display correction
E2:51
Display correction +0.1 K
to
to
E2:99
display correction +4.9 K
F1:1
Screed drying adjustable, with
to
choice of 6 temperature/time profiles
F1:6
(see page 78)
F1:15
Constant flow temperature 20 °C
(see page 78)
F2:0
No time limit
F2:1
Time limit adjustable from 1 to
to
12 h
*1
F2:12
F8:+10
Outside temperature limit adjustable
to
from
F8:–60
+10 to
F8:–61
Function disabled.
F9:+10
Outside temperature limit adjustable
to
from +10 to
F9:–60
FA:0
Temperature rise adjustable from 0
to
to 50 %.
FA:50
Fb:0
Time period adjustable from 0 to
to
300 min.
Fb:150
1 step
(cont.)
5 K
0.1 K
*1
.
60 °C.
60 °C
2 min.