Viessmann VITOTRONIC 200 Installation And Service Instructions Manual page 49

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

"Solar" group
(cont.)
Coding in the delivered condition
10:0
Target temperature control switch-
ed off (see coding address "11")
11:50
Set solar DHW temperature 50 °C
Target temperature control
switched on (code "10:1"):
Temperature at which the solar
heated water is to be stratified
into the DHW cylinder.
Code "20:9" (heating of 2 DHW
cylinders) is set:
When the set DHW temperature
is achieved in one DHW cylinder,
the 2nd DHW cylinder is heated.
12:20
Minimum collector temperature
(minimum start temperature for the
solar circuit pump) 20 °C
20:0
No extended control function ena-
bled.
22:8
Start temperature differential with
central heating backup (code
"20:4" must be set) 8 K
23:4
Stop temperature differential with
central heating backup (code
"20:4" must be set) 4 K
24:40
Start temperature for thermostat
function (code "20:5" or "20:6"
must be set) 40 °C
25:50
Stop temperature for thermostat
function (code "20:5" or "20:6"
must be set) 50 °C
26:1
Priority for DHW cylinder 1 with
cyclical heating
(code "20:9" must be set)
Possible change
10:1
Target temperature control switched
on
11:10
The set solar DHW temperature is
to
adjustable from 10 to 90 °C.
11:90
12:0
No minimum limit enabled
12:1
Minimum collector temperature ad-
to
justable from 1 to 90 °C.
12:90
20:1
Additional function for DHW heating
20:2
Differential temperature control 2
20:3
Differential temperature control 2
and auxiliary function
20:4
Differential temperature control 2 for
central heating backup
20:5
Thermostat function
20:6
Thermostat function and auxiliary
function
20:7
Solar heating via external heat ex-
changer without additional tempera-
ture sensor
20:8
Solar heating via external heat ex-
changer with additional temperature
sensor
20:9
Solar heating of 2 DHW cylinders
22:2
Start temperature differential adjust-
to
able from 2 to 30 K
22:30
23:2
Stop temperature differential adjust-
to
able from 1 to 29 K
23:30
24:0
Start temperature for thermostat
to
function adjustable from 0 to 100 K
24:100
25:0
Stop temperature for thermostat
to
function adjustable from 0 to 100 K
25:100
26:0
Priority for DHW cylinder 1 without
cyclical heating
26:2
Priority for DHW cylinder 2 without
cyclical heating
26:3
Priority for DHW cylinder 2 with cy-
clical heating
26:4
Cyclical heating without priority for
one of the DHW cylinders
Coding level 2
49