Function Description Boiler Water Temperature Control; Brief Description; Functions - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Weather-compensated, digital boiler control unit
Table of Contents

Advertisement

Function description
Boiler water temperature control

Brief description

The boiler water temperature is regulated by starting
or stopping the burner or through modulation. In the
delivered condition, the switching differential is
relative to the current set value.
The set boiler water temperature is determined from
the following parameters:
Set flow temperature of the heating circuits con-
nected to the control unit and the heating circuits
connected via the LON BUS
External demand
Set DHW temperature

Functions

The boiler water temperature is captured by the follow-
ing equipment:
High limit safety cut-out STB (liquid expansion)
Temperature controller TR (liquid expansion)
Boiler water temperature sensor NTC 10 k
Upper control range limits:
High limit safety cut-out STB 110/100/95 °C
Temperature controller TR 75/87/95 °C
Electronic maximum temperature limit:
Setting range: 20 to 127 °C
Changed via coding address "06" in the "Boiler"
group.
The limit is only effective within the control range
(not for DHW cylinder heating).
Lower control range limits:
In standard mode and when frost protection is ena-
bled, the boiler water temperature will be regulated
subject to the respective boiler.
Auxiliary circuits
Extension for controlling a two-stage/modulating
burner (see page 21).
External hook-ups (messages) via EA1 extension
(see page 91).
Plug "X12" for external burner start (see page 18).
Plug
for external demand (see page 19) or exter-
lH
nal blocking (see page 20).
Switching hysteresis, burner
Permanent switching hysteresis
Code "04:0"
76
The boiler coding card specifies a minimum boiler
water temperature that must be maintained to protect
2 K,
the boiler.
±
When the DHW cylinder is heated, the default set
boiler water temperature is 20 K above the set DHW
temperature (adjustable via coding address "60" in
the "DHW" group).
ON
OFF
+2
Ω
set
-2
low
heat demand
Fig.40
Heat demand-dependent switching hysteresis
The heat demand-dependent switching hysteresis
takes the boiler utilisation level into account.
The switching hysteresis, i.e. the burner runtime, var-
ies subject to the current heat demand.
ERB50 function
Code "04:1"
Depending on the heat demand, values between 6 and
12 K result.
ON
OFF
+9
+3
set
-3
low
heat demand
Fig.41
ERB80 function
Code "04:2"
Depending on the heat demand, values between 6 and
20 K result.
average
high
heat demand
heat demand
average
high
heat demand
heat demand
Time
Time