Dhw" Group; Solar" Group - Viessmann Vitotronic 300 GW6B Installation Instructions Manual

Weather-compensated boiler and heating circuit control unit in single boiler or multi boiler systems
Table of Contents

Advertisement

Vitotronic 300, GW6B Installation and Service

"DHW" Group

Coding in the factory set condition
"Storage tank heating, hysteresis"
55:0
Tank heating hysteresis ± 2.5 K
"For solar DHW heating: DHW temperature target"
67:40
DHW setpoint temperature 104°F (40°C).
Reheating is suppressed above the selected
set temperature (DHW heating blocked by the
boiler).
"DHW recirculation pump"
73:0
ON according to time program

"Solar" Group

Note: The "Solar" group is only displayed if a solar control module, type SM1, is connected.
Coding in the factory set condition
"Solar circuit pump speed control"
02:0
Solar circuit pump is not speed controlled
"Maximum storage tank temperature"
08:60
DHW setpoint temperature (maximum tank
temperature) 140°F (60°C)
"Stagnation time reduction"
0a:5
Temperature differential for stagnation time
reduction (reduction in the speed of the solar
circuit pump to protect system components
and heat transfer medium) 5 K.
"Solar circuit flow rate"
0f:70
Solar circuit flow rate at maximum pump
speed 1.8 USG/min (7 L/min)
"Extended control function"
20:0
No extended control function enabled
Possible change
55:1
Adaptive storage tank heating enabled
(see page 82)
55:2
Storage tank temperature control with 2
temperature sensors (see page 82).
55:3
Storage tank temperature control, storage tank
loading system (see page 83)
67:0
Adjustable from 32 to 203°F (0 to 95°C)
to
(limited by boiler-specific coding)
67:95
73:1
"ON" from once per hour for 5 min up to
to
6 times per hour for 5 min during the time
73:6
program.
73:7
Permanently ON
Possible change
02:1
Variable speed solar circuit pump with wave
packet control
02:2
Solar circuit pump speed controlled with PWM
control
08:10
Adjustable from 50 to 194°F (10 to 90°C)
to
08:90
0a:0
Stagnation time reduction disabled
0a:1
Temperature differential adjustable from
to
1 to 40 K
0a:40
0f:1
Adjustable from 0.02 to 6.7 USG/min
to
(0.1 to 25.5 L/min),
0f:255
1 step
20:1
Additional function for DHW heating
20:2
Differential temperature control 2
20:3
Differential temperature control 2 and auxiliary
function
20:4
Differential temperature control 2 for central
heating backup
20:5
Thermostat function
20:6
Thermostat function and auxiliary function
20:7
Solar heating via external heat exchanger
without additional temperature sensor
20:8
Solar heating via external heat exchanger with
additional temperature sensor
20:9
Solar heating of two DHW storage tanks
[Solar heating of two DHW tanks]
Coding level 1
0.02 USG/min (0.1 L/min).
91