Solar" Group - Viessmann VITOTRONIC 200 Installation And Service Instructions Manual

Type ho1b & mw2b, digital boiler control unit & weather-compensated, digital cascade control unit
Table of Contents

Advertisement

Vitotronic 200 and 300-K Installation and Service

"Solar" Group

Coding
Coding in the factory set condition
Speed control solar circuit pump
02:0
Solar circuit pump (multi stage) without speed
control by solar control module SM1.
DHW tank maximum temperature
08:60
The solar circuit pump stops when the actual
DHW temperature reaches the maximum
DHW tank temperature 140° F (60° C).
Stagnation time reduction
0A:5
To protect system components and heat
transfer medium: the speed of the solar
circuit pump is reduced if the actual DHW
temperature is 5 K below the maximum DHW
tank temperature.
Flow rate solar circuit
0F:70
The solar circuit flow rate at maximum pump
speed is 7 L/min.
20:0
No extended control functions enabled.
Note: The solar group is only displayed if a solar control
module, type SM1, is connected.
Possible change
02:1
Solar circuit pump (multi stage) is speed-
controlled with wave pack control.
02:2
Solar circuit pump is speed-controlled with PWM
control.
08:10
The maximum DHW tank temperature
to
is adjustable from 50 to 194° F (10 to 90° C).
08:90
0A:0
Stagnation time reduction is disabled.
0A:1
Value for stagnation time reduction is adjustable
to
from 1 to 40 K.
0A:40
0F:1
Flow rate adjustable from 0.1 to 25.5 L/min;
to
1 step
0.1 L/min.
0F:255
20:1
Additional function for DHW heating.
20:2
Differential temperature control 2.
20:3
Differential temperature control 2 and auxiliary
function.
20:4
Differential temperature control 2 for central
heating backup.
20:5
Thermostat function.
20:6
Thermostat function and auxiliary function.
20:7
Solar heating via external heat exchanger
without additional temperature sensor.
20:8
Solar heating via external heat exchanger
with additional temperature sensor.
20:9
Solar heating of two DHW tanks.
Code 1