Leuze electronic MA 258i Operating Instructions Manual page 19

Fieldbus gateway - ethernet/ip
Table of Contents

Advertisement

Attention!
If the configuration assembly is addressed with instance 118 and length 12 in the input mask
for the generic module, all MA
moment. All default parameters of the MA must be manually entered in the configuration
assembly. Changing the individual default values is possible at any time.
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 12.6.2.
The query cycle of the input and output assemblies is subsequently defined in the Module
properties -> Connection path in the Request packet interval (RPI) input field.
The participant is thereby defined in offline mode; the data must subsequently be transferred
to the control.
Configuration of the participant using the EDS file
From RSLogix 5000 software version 20.00 and up, proceed as follows to create the
MA
258i
as an EtherNet participant in your system:
 First, load the EDS file for the device via EDS wizard into the PLC database.
Notice!
You can find the EDS file at www.leuze.com.
 After loading, select the device via the device list and enter it into the HW manager via
Drag&Drop.
 Open the input dialog for setting the address and additional parameters by double-click-
ing on the device symbol and make the desired entries here.
 Finally, transmit the values to the device via download.
Leuze electronic
Fast commissioning / operating principle
258i
parameters with the value 0 are occupied in the first
MA
258i
17