Transfer The Data To The Control (Rslogix 5000 Specific); Adapting The Device Parameters - Leuze electronic MA 258i Operating Instructions Manual

Fieldbus gateway - ethernet/ip
Table of Contents

Advertisement

Fast commissioning / operating principle
3.5.3

Transfer the data to the control (RSLogix 5000 specific)

 Activate online mode.
 Select the EtherNet communication port.
 Select the processor onto which the project is to be transferred.
 Set the control to PROG.
 Start the download.
 Set the control to RUN.
3.5.4

Adapting the device parameters

Configure the parameters via the config assembly
The MA
258i
of the MA
258i
The config assembly must include all parameters that affect the MA 258i. The config
assembly is automatically written to the connected participants in cycles that the control
manufacturer defines.
The config assembly is implemented in class 4, under instance 118. By default, all param-
eters are preset to the value 0 (zero).
Attention!
If the config assembly is not adapted, the MA
to the parameters preset with 0.
 Switch the control to offline mode.
 Double-click
The configuration assembly can be recognized by the index "C" appended to the device
name.
Parameter entry is performed as described in section "Setting MA parameters manually via
the config assembly" on page 74.
Attention!
Activation of the config assembly as described above necessitates value entry in the corre-
sponding parameter memory locations. When using the configuration assembly, the default
parameters must also be entered in the corresponding memory locations (see also "Setting
MA parameters manually via the config assembly" on page 74).
After all of the parameters relevant to the MA
"online" and the project is downloaded again.
18
makes available a configuration assembly that allows the entire parameter set
to be saved in the control and, if necessary, to be called up.
Controller tags
258i
displays a corresponding behavior acc.
to edit the configuration assembly.
258i
are entered, the control is switched to
MA
258i
Leuze electronic

Advertisement

Table of Contents
loading