Fast commissioning / operating principle
Figure 3.5:
The input mask for the Generic module describes:
• The name of the participant (can be selected freely; e.g.MA 258i).
• The format of the I/O data (data - DINT = 32bit or data - SINT = 8bit).
• The IP address of the participant.
• The address and length of the input assembly (instance 106). *)
• The address and length of the output assembly (instance 107). *)
• Optional: The address and length of the configuration assembly (instance 118; 12 x
8bit).
*) The possible data lengths are shown in figure 3.5. You can select the suitable byte
number for your application here. Recommendations can be found in chapter "Spec-
ifications for Leuze end devices" on page 97.
Notice!
The available lengths (4, 8, 12, 16, 20, 32, 64, 128, 240 bytes) of the input/output data cannot
be freely combined. The MA can only process ONE combination (connection). Please select
the suitable combination for the data length and the connected device. Detailed information
on this topic can be found in chapter 12.6.2.
16