Detailed Description Of The Bits (Output Byte 1) - Leuze electronic MA 258i Operating Instructions Manual

Fieldbus gateway - ethernet/ip
Table of Contents

Advertisement

10.3.3 Detailed description of the bits (output byte 1)

Bit 0: Read-Acknowledge: R-ACK
This bit is only relevant for writing slave data in blocks (Collective mode), see chapter 11.1.2.
Output data
R-ACK
Bit 2: Send data from buffer: SFB
This bit is only relevant for writing slave data in blocks (Collective mode), see chapter 11.1.2.
Output data
SFB
Leuze electronic
Description
Read-Acknowledge
(read confirmation)
Toggle bit: Indicates to the fieldbus gateway that the "old"
data has been processed and that new data can be
received. At the end of a read cycle, this bit must be toggled
in order to be able to receive the next data set. This toggle
bit is switched by the master after valid received data has
been read out of the input bytes and the next datablock can
be requested. If the gateway detects a signal change in the
R-ACK bit, the next bytes are automatically written from the
receive buffer to the input data words and the BLR bit tog-
gled. Further toggling erases the memory (to 00h).
Description
Send data from buffer
(send data from the gateway transmit buffer to the RS 232)
Toggle bit: changing this bit causes all data which was copied
to the transmit buffer of the fieldbus gateway via the CTB bit
to be transmitted to the RS 232 interface or the connected
Leuze device.
Addr. Data
1.0
Addr. Data
1.2
MA
258i
Telegram
Value range
type
0->1 or
1->0: Successfully
Bit
written & ready for
the next transmis-
sion
Value range
type
0->1: Data to
RS 232
Bit
1->0: Data to
RS 232
Default
0
Default
0
59

Advertisement

Table of Contents
loading