Quick Menu Summary; Language - Danfoss Cascade Operating Instructions Manual

Controller option
Table of Contents

Advertisement

Quick Menu Summary

Quick Menu
Parame-
Name
number
ter num-
ber
Basic Drive Set Up parameters
001
001

Language

002
102
Motor Power
003
103
Motor Voltage
004
104
Motor Frequency
005
105
Motor Current
006
106
Rated Motor Speed
007
201
Min. Frequency
008
202
Max. Frequency
009
206
Ramp up time
010
207
Ramp down time
011
323
Relay 1 Output
012
326
Relay 2 Output
Basic Set Up for Standard Cascade and Master/Slave.
013
415
Closed loop units
014
413
Minimum Feedback
015
414
Maximum Feedback
016
227
Warning low Feedback
017
228
Warning high Feedback
018
204
Ref.min.
019
205
Ref.max.
020
723
Operational Mode select
021
712
Pump combination
022
713
Staging BandW.
023
714
Destaging Delay
024
715
Staging Delay
025
716
Override BW
026
717
Override Timer
027
718
Transition frequency
028
418
Setpoint 1 (H0)
029
419
Setpoint 2 (H1)
030
721
Destage Timer
031
722
Pump cycling
032
319
Analog/digital outputs
033
739
M/S Stage on frequencies
034
740
M/S stage off frequencies
PID Controller tuning
035
420
Normal/Inverse control
036
422
PID Start up frequency
037
427
PID Lowpass filter time
038
423
PID Proportional Gain
039
424
PID Integrator time
Language
Quick Menu 001 Par. 001 Language
(LANGUAGE)
Value:
English (ENGLISH)
German (DEUTSCH)
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option
Units
Range
10 languages
KW/HP
1.1-450/1.5-600
Volts
200 - 480
Hz
50 / 60
Amps
0-IVLT max
RPM
0- fm,n x 60
Hz
0.0 -fmax
Hz
Fmin-120/1000
Seconds
1-3600
Seconds
1-3600
Depending on choice
Selected according to your process.
Units
-999,999.999- FB High
Units
FB low- 999,999.999
Units
Min. feedback - Ref.max
Units
Ref.min - Max. feedback
-
Standard / M/S
1 - 8
%
1.0 - 100.0
Sec.
0.0 - 3000
Sec.
0.0 - 3000
% of set point
2.0 - 100.0
Sec.
0.0 - 300
% of fnom
fmin - 120.0
Bar (or equiv.)
Refmin - Refmax
Bar (or equiv.)
Refmin - Refmax
Timer Sec.
0.0 - 600
Enabled/Disabled
-
[1] - [43]
Hz
F min - F max
Hz
F min - F max
Normal/Inverse
Hz
Fmin-fmax
Sec.
0.01 10.00
Factor
0.00 10.0
Sec.
0.01 9999.0
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
Swedish (SVENSKA)
Dutch (NEDERLANDS)
Factory setting
See VLT 6000 HVAC or VLT
8000 AQUA manuals.
2/5 of fnom (NEW)
Fnom x 1.1 (NEW)
See table above in 2.4.8
See VLT 6000 HVAC Manual.
-999,999.999
999,999.999
0
0
Standard Cascade
1
10.0
15
15
20.0
5
60
6 bar
6 bar
30
Enabled
F out 020mA
F min
F max
Normal mode
0 Hz
1.00
0.01
OFF
29