Danfoss Cascade Operating Instructions Manual page 51

Controller option
Table of Contents

Advertisement

reference signal for control. See the VLT Operating
Manual for additional information.
Quick Menu 028 Par. 418 Setpoint 1
(SETPOINT 1)
Value:
Feedback Min. to Feedback Max.
Function:
Setpoint 1 is used to provide the setpoint reference
for one setpoint PID control or for the setpoint for
zone 1 in two setpoint PID control.
Description of choice:
Set the required value the system is to maintain
during normal operation. The value must be between
the minimum and maximum values set in Quick
Menu items 14 and 15 (parameter 413, Minimum
Feedback, and parameter 414, Maximum Feedback).
Setpoint 2, Quick Menu item 29, is not used in
one feedback signal applications.
MG.60.I3.02 - VLT is a registered Danfoss trademark
Cascade Controller Option