Chapter 2 Parameter Settings; Procedure For Setting Parameters - Mitsubishi Electric MELSEC iQ-R Series User Manual

Ethernet/ip network interface module, application
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2
PARAMETER SETTINGS
This chapter describes the parameter settings required for communications between the RJ71EIP91 and EtherNet/IP devices.
2.1

Procedure for Setting Parameters

1.
Add the RJ71EIP91 in the engineering tool.
[Navigation window]
2.
The basic settings, application settings, and refresh settings are included in the module parameters. Select the settings
from the navigation tree in the following window and configure them.
[Navigation window]
3.
Use the engineering tool to write the module parameters to the CPU module.
[Online]
[Write to PLC]
4.
The settings are reflected by resetting the CPU module or powering off and on the system.
5.
Start EtherNet/IP Configuration Tool, and then set the EtherNet/IP communication parameters.
6.
Use EtherNet/IP Configuration Tool to write the EtherNet/IP communication parameters to the RJ71EIP91.
[Parameter]
[Module Information]
[Parameter]
[Module Information]
Right-click
[Add New Module]
[RJ71EIP91]
2 PARAMETER SETTINGS
2.1 Procedure for Setting Parameters
2