Setting method
For Class1 tag communications, set the Producer Tag and the Consumer Tag on the RJ71EIP91 on the Producer side and the
RJ71EIP91 on the Consumer side.
■Common settings
Set the IP address, subnet mask, and default gateway of the RJ71EIP91 on the Producer side and the RJ71EIP91 on the
Consumer side.
[Navigation window]
For details on the setting window, refer to the following.
Page 44 Basic Setting
■Settings of the RJ71EIP91 on the Producer side
Use EtherNet/IP Configuration Tool to register the RJ71EIP91(1) on the Producer side. Then, set the tag communications.
For details on registering the RJ71EIP91 on the Producer side, refer to the following.
Page 94 Procedure for Registering EtherNet/IP Devices
The EDS file of the RJ71EIP91 on the Producer side can be found in the compressed file in which the installer
of EtherNet/IP Configuration Tool is stored.
Set the RJ71EIP91 on the Producer side from the window shown below.
Select the "RJ71EIP91" in the network configuration settings.
(1) Tag name
(2) Data Size
(3) Trigger type
(4) RPI
1 FUNCTIONS
32
1.1 EtherNet/IP Communication Functions
[Parameter]
[Module information]
[RJ71EIP91]
(1)
[Device]
[Basic Setting]
[Properties]
[Connections] tab
(1)
(2)
(3)
(4)