Mitsubishi Electric MELSEC iQ-R Series User Manual page 94

Ethernet/ip network interface module, application
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Setting window on the Consumer Tag side
Select "Target (Class1 Tag)" in the network configuration settings.
Item
Device Designation
Producer Tag
*1 Characters from A to Z, numbers from 0 to 9, "." (dot), "-" (hyphen), and "_" (underscore) can be used. For the first character of a name,
only characters from A to Z can be used.
*2 Only even numbers can be set.
3 EtherNet/IP Configuration Tool
92
3.1 Window Structure
Description
Device Name
Sets the name to use in management with EtherNet/IP
Configuration Tool.
By default, names of EtherNet/IP devices not registered in the
network configuration setting are displayed in the form such as
"DEVICE-A" and "DEVICE-B".
Number
Sets the control number of the EtherNet/IP device.
The control number that has not been set for EtherNet/IP devices
can be selected from the list.
Active Configuration
Enables or disables the parameters set for the EtherNet/IP device
on the RJ71EIP91.
• Selected: Enabled
• Not selected: Disabled
Disable this item when the parameters of the EtherNet/IP device
need to be deleted from the RJ71EIP91 with the settings in
EtherNet/IP Configuration Tool held.
Clearing of this check box is reflected against 'Reserved station
(Class1)' (Un\G27168 to Un\G27183) on the RJ71EIP91.
Comment
Displays the comment input field.
Connection No
Displays the connection number of the EtherNet/IP device.
Connection numbers of EtherNet/IP devices are assigned from 1
in the order in which they were added.
Tag Name
Specifies the tag name used in Class1 tag communications.
Size
Specifies the data size used in Class1 tag communications. (Unit:
Bytes)
[Device]
[Properties]
Setting range
Up to 50 characters
(Default: Refer to the left.)
000 to 255
(Default: Minimum value of the
control numbers of EtherNet/IP
devices that have not been
set)
(Default: Selected)
Up to 255 single-byte
characters
(Default: Blank)
Up to 255 single-byte
characters
(Default: Blank)
2 to 1444
(Default: 2)
*1
• Selected
• Not selected
*2

Hide quick links: