Mitsubishi Electric MELSEC iQ-R Series User Manual page 64

Ethernet/ip network interface module, application
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

"Online Action" window
The "Online Action" window is used to perform Class3 message communications and UCMM message communications.
Items in this window can be used when EtherNet/IP Configuration Tool is switched to the online state. ( Page 50 File)
Select the [Network Detection] tab.
■[Explicit Message] tab
Use this tab when performing message communications with an EtherNet/IP device.
Item
Address
IP Address
Class
Instance
Attribute
Service
Number
Name
Enter Path
Data
[Send to Device] button
Continue (500ms)
3 EtherNet/IP Configuration Tool
62
3.1 Window Structure
[Network]
Description
Specifies the IP address of the EtherNet/IP device to perform Class3
communications and UCMM communications with.
The valid range of IP address is 0.0.0.1 to 223.255.255.254.
Specifies the class ID for performing message communications.
Specifies the instance ID for performing message communications.
Specifies the attribute ID for performing message communications.
Specifies the service value for performing message communications.
This item cannot be entered if a value other than "Customer Service" is
specified for "Name".
Specifies the service for performing message communications.
To specify the service that is not displayed in this item, specify "Customer
Service", and specify a value for "Number".
Although there are other setting items than those described to the right,
they are not supported on the RJ71EIP91.
*2
When this check box is selected, the following items can be input.
• Identifier of CIP object
• Instance
• Attribute of instance
Enters the data to send to the EtherNet/IP device.
Starts Class3 communications and UCMM communications.
When this check box is selected, Class3 communications and UCMM
communications will be executed repeatedly at intervals of 500ms.
[Online Action]
*1
Setting range
0.0.0.0 to 255.255.255.255
(Default: Current IP address of the
EtherNet/IP device)
0 to 65535
(Default: 0)
0 to 65535
(Default: 0)
0 to 65535
(Default: 0)
0 to 255
(Default: 14)
• Customer Service
• Get_Attributes_Single
• Set_Attributes_Single
• Get_Attributes_All
(Default: Get_Attributes_Single)
• Selected
• Not selected
(Default: Not selected)
• Selected
• Not selected
(Default: Not selected)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-rj71eip91

Table of Contents