Program Example - Mitsubishi Electric MELSEC iQ-R Series User Manual

Ethernet/ip network interface module, application
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Program example

The following example shows a program to execute the PING test by turning on the PING test request command in the
program.
Classification
Label name
Module label
EIP91_1.bSts_ModuleReady
EIP91_1.bSts_PingTestComplete
EIP91_1.bSet_PingTestRequest
EIP91_1.uSet_PingTestRequest_CommunicationTimeCheck_D
EIP91_1.uSet_PingTestRequest_TransmissionsCount_D
EIP91_1.unSet_PingTestRequest_IPAddress_D[0]
EIP91_1.unSet_PingTestRequest_IPAddress_D[1]
EIP91_1.unArea_PingTestReceiveResulteArea_D[0]
EIP91_1.unArea_PingTestReceiveResulteArea_D[1]
EIP91_1.unArea_PingTestReceiveResulteArea_D[2]
EIP91_1.unArea_PingTestReceiveResulteArea_D[3]
Label to be defined
Define global labels as shown below.
4 PROGRAMMING
108
4.2 Program Example of PING Test
Description
Module Ready
PING test completion
PING test execution request
PING test request area
Communication time check
PING test request area
Transmission count
PING test request area
IP Address (lower)
PING test request area
IP Address (upper)
PING test result area
Result
PING test result area
Total Number of packet
transmissions
PING test result area
Number of success
PING test result area
Number of failure
Device
X0
X12
Y12
U0\G27904
U0\G27905
U0\G27906
U0\G27907
U0\G27908
U0\G27909
U0\G27910
U0\G27911

Hide quick links: