• I/O data window
Item
Input
[..] button
Length(bytes)
Status
Output
[..] button
Length(bytes)
Status
I/O data of connections that exceed 1400 bytes is not displayed in the I/O data window.
To check I/O data of connections that exceed 1400 bytes, refer to the following.
• Class1 input data area (Un\G65536 to Un\G98303)
• Class1 output data area (Un\G196608 to Un\G229375)
• Status value
The following table lists the values of the "Input Status", "Output Status", and "Status" displayed in the diagnostic information
window and I/O data window.
When the RJ71EIP91 is scanner
Status value
0
33
53
54
58
65
68
69
70
77
When the RJ71EIP91 is adapter
Status value
0
33
53
54
69
3 EtherNet/IP Configuration Tool
88
3.1 Window Structure
Description
Changes the display format of the input data.
Displays the size of the input data. (Unit: Bytes)
Displays the Status value of the input connection.
Changes the display format of the output data.
Displays the size of the output data. (Unit: Bytes)
Displays the Status value of the output connection.
Description
EtherNet/IP communications are being performed normally.
A timeout has occurred.
An Idle notification has been received from the EtherNet/IP device.
EtherNet/IP communication connection has been established and no communications are performed.
An EtherNet/IP communication error (TCP error) has occurred.
An EtherNet/IP communication error (CIP error) has occurred.
EtherNet/IP communication connection processing is in progress.
Set as a reserved station.
An EtherNet/IP communication error (CIP error) has occurred.
EtherNet/IP communication is stopping.
Description
EtherNet/IP communications are being performed normally.
An EtherNet/IP communication error is occurring.
An Idle notification has been received from the EtherNet/IP device.
EtherNet/IP communication connection has been established and no communications are performed.
Set as a reserved station.