■Application Trigger and Change of State
Data sending with Application Trigger or Change of State is executed by turning off and on 'Application Trigger Request
(Class1)' (Un\G27008 to Un\G27023).
When data is sent with Application Trigger, whether or not to send the data automatically can be selected by 'Application
Trigger operating specification Request (Class1)' (Un\G16631). When data is sent with Change of State, this setting is
ignored.
The following table lists the setting items of Application Trigger and Change of State.
Type
Application Trigger
Change of State
*1 When Default is set, a quarter of RPI is specified as the inhibit time.
*2 When Un-Activated is set, no inhibit time is specified.
1 FUNCTIONS
34
1.1 EtherNet/IP Communication Functions
Setting item of EtherNet/IP Configuration Tool
Trigger Type
Inhibit time setting
Inhibit Time Mode
Application
 (No setting)
*1
Change of State
Default
Un-Activated
Custom
Inhibit time(ms)
 (No setting)
 (No setting)
*2
 (No setting)
Specifies in the range
between 1 and 255.
Buffer memory
'Application Trigger Request
(Class1)' (Un\G27008 to Un\G27023)
Off → On
Off → On
Off → On
Off → On