PROFIBUS DP communication

9.1.4.1 PROFIBUS DP configuring

The ASM 452 is integrated into the hardware configuration by means of a GSD file. The
ASM can then be configured using the HW Config of SIMATIC Manager or another
PROFIBUS DP tool.
A GSD file is provided for ASM 452 on the "MOBY software" CD.

9.1.4.2 Operating mode of the ASM 452

The approved operating modes of ASM 452 are described in the GSD file. It is set using the
hardware configuration tool (e.g. STEP 7 HW Config).

9.1.4.3 PROFIBUS DP diagnostics

The following table lists possible error indications with their meanings and provides
remedies.
Table 9- 2
"BF" LED
On
flashes
flashes
On
MOBY D
System Manual, 01/2010, J31069-D0147-A6-7618
LED indication for PROFIBUS DP diagnostics
"SF" LED
Cause of error
ASM 452 is in start-up mode.
*
Communication to the DP master
is down.
ASM 452 not detecting a baud
rate.
Bus interruption
DP master is out of service
The configuration data sent to
On
the ASM 452 by the DP master
do not match the configuration of
the ASM 452.
ASM 452 has detected the baud
off
rate, but is not being addressed
by the DP Master.
ASM 452 has not been
configured.
There is a hardware defect in the
flashes
ASM 452.
System integration
9.1 ASM 452
Error management
-
Check the PROFIBUS DP
connection.
Check the DP master.
Check all cables on your
PROFIBUS DP network.
Check whether the connector
plugs for PROFIBUS DP are
securely plugged into the
ASM 452.
Check the configuration of
the ASM 452 (input/output,
PROFIBUS DP address).
Correct GSD file being used?
SIEM80B6.GSD for
ASM 452
Check the PROFIBUS DP
address set on the ASM 452
or in the configuration
software.
Check the configuration of
the ASM 452 (station type).
Replace the ASM 452.