11.2 Error messages and causes for MOBY D with ASM and FC/FB 45 (direct MDS addressing)
Error code
(B#16#..)
0A
0B
0C
0D
MOBY D
System Manual, 01/2010, J31069-D0147-A6-7618
Description
Another init_run was started without waiting for ready during execution of the
init_run command
not
Do
set init_run cyclically
The same physical ASM channel is used in two (or more) UDT 10 structures.
Check ASM_address and ASM_channel in
init_run cannot be executed; cyclic Process image for ASM is faulty; FC/FB 45
signals timeout of process image to ASM
This error can be deactivated by writing the value #00 to address DBB 58 in UDT
10. In certain error situations, FC/FB 45 will then, however, not generate an error
message and "seize up".
ASM_address in UDT 10 is parameterized incorrectly. ASM_address may be for
wrong module.
ASM_channel setting is ≥16 or ≤0
ASM hardware/firmware is faulty.
The same physical ASM channel is used in two (or more) UDT 10 structures.
Check ASM_address and ASM_channel in
Area length error on block move for FC/FB 45.
DAT_DB does not exist or is too small. Check DAT_DB_number and
DAT_DB_address in UDT 20
Execute an init_run
An init_run was not completed correctly. The process image is not consistent.
Run init_run again
Turn ASM off and on again.
The RUN/STOP switch on the CPU was pressed rapidly several times in
succession (particularly with slow PROFIBUS DP baud rates)
The same physical ASM channel is used in two (or more) UDT 10 structures.
Check ASM_address and ASM_channel in
Alarm, error and system messages
all
UDT 10 structures.
all
UDT 10 structures.
all
UDT 10 structures.