Fast Commissioning (Quick Start) With Siwatool; Service With The Siwatool Program; Establish Communication To Siwarex Wp321 - Siemens SIWAREX WP321 Operating Instructions Manual

Electronic weighing system
Hide thumbs Also See for SIWAREX WP321:
Table of Contents

Advertisement

7.4

Fast commissioning (Quick Start) with SIWATOOL

7.4.1

Service with the SIWATOOL program

You can use the SIWATOOL program to commission the scale independent of the SIMATIC
automation system. The program is included in the configuration package.
Install the SIWATOOL program (SIWATOOL folder) on your PC for commissioning.
The SIWATOOL program is described in the sectionService with the SIWATOOL program
(Page 56).
You require an RS485-USB converter from Siemens in order to connect the PC to the
SIWAREX (see section Ordering data (Page 123)). You can then connect the RS485 interface
of the SIWAREX to the USB port of the PC.
● Close the RS485-USB converter proposed by Siemens (see section Ordering data
(Page 123)) at the base unit of SIWAREX WP321 as follows:
RS485-USB converter
Terminal A
Terminal B
Terminal X
-
-
7.4.2

Establish communication to SIWAREX WP321

● After starting the SIWATOOL program, select the SIWAREX WP321 from the "Device
selection" window.
Figure 7-8
● Select the menu command "Communication" > "Choose interface".
SIWAREX WP321
Operating Instructions, 08/2019, A5E33715669A-AD
SIWATOOL: Device selection window
7.4 Fast commissioning (Quick Start) with SIWATOOL
Base unit of SIWAREX WP321
Terminal 13 (D+)
Terminal 14 (D-)
-
Bridge between terminals 9 (T+) and 11 (D+')
Bridge between terminals 10 (T-) and 12 (D-')
Commissioning
45

Advertisement

Table of Contents
loading

Table of Contents