Mounting Position

3-1

Mounting Position

3-1-1 C1000H

3-1-2 C2000H

3-1-3 C200H/C200HS

18
Note
1. Turn off power to the PC before mounting Units to the Backplane.
2. Tighten Backplane mounting screws firmly.
The C1000H-SLK11/SLK21-V1 can be mounted in one of the first three slots
to the left of (i.e., next to) the CPU Unit when using the 3G2A5-BC081/051
Backplane, and in one of the first five slots to the left of the CPU Unit when
using a C500-BC082/052 Backplane.
CPU Rack
I/O
Control
Unit
C1000H-SLK11/SLK21-V1 can be mounted in any slot in 3G2C5-BC061
Backplanes.
CPU Rack
I/O
Control
Unit
3G2C5-BC061
Any slot
The C200HW-SLK13/14/23/24 must be mounted in one of the two slots
immediately to the left of the CPU Unit when using the C200H-BC081-V2 or
C200H-BC051-V2 Backplane.
3G2A5-BC081/051 Backplane:
Mount only in one of the three slots
immediately to the left of the CPU Unit.
CPU
Unit
C500-BC082/052 Backplane:
Mount only in one of the five slots
immediately to the left of the CPU Unit.
Power
CPU
Supply
Unit
Unit
Section 3-1
Power
Supply
Unit