This section provides general precautions for using the SYSMAC C-series Link Adapters and related devices. The information contained in this section is important for the safe and reliable application of the Link Adapters. You must read this section and understand the information contained before attempting to set up or operate the Link Adapters.
It is extremely important that the Link Adapter be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying the Link Adapter system to the above-mentioned applications.
Application Precautions WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock. Operating Environment Precautions Caution Do not operate the control system in the following locations: Caution Take appropriate and sufficient countermeasures when installing systems in the following locations:...
Page 10
Application Precautions Caution Failure to abide by the following precautions could lead to faulty operation of the Link Adapters or the system, or could damage the Link Adapters or the system. Always heed these precautions. Observe the following precautions when using the Link Adapter system. Tighten the screws on the terminal block of the AC Power Supply Unit to the torque specified in the operation manual.
This document is designed to introduce the reader to the principles of Link Adapters and Repeater Units. Link Adapters and Repeater Units are connecting devices for SYSMAC C-Series Programmable Controllers. Link Adapters are used to interconnect system devices such as host computers, PC Link Units, Host Link Units, and Remote I/O Units, and/or to convert back and forth between wire cable and optical fiber cable.
Link Adapters Nomenclature Names of specific OMRON products, as well as generic names for groups of OMRON products, are capitalized in this manual. Unit is also capitalized when it refers either specifically or generically to an OMRON product. For convenience, prefixes are omitted from model numbers of Link Adapters and Repeater Units.
General Specifications Repeater Units Repeater Units are used when the number of Optical Transmitting I/O Units, Op- tical Slave Racks, etc., connected in series exceeds 32. Insertion of a Repeater Unit after the 32nd Unit allows the connection of additional Units. The following Repeater Units are used with the cables shown here: APF: All-plastic optical fiber cable PCF: Plastic-clad optical fiber cable...
Page 14
General Specifications Repeater Units Model Function RPT01-P, Used when more than 32 Optical Transmit- ting I/O Units, Slave Racks, etc., are con- RPT01 nected in series. Supply voltage Operating voltage range 100 to 120/200 to 85 to 264 VAC 240 VAC or 12 to 24 VAC/DC Section Power...
RS-422 and RS-232C Cable Power Supply and Cable Lengths Power Supply For all but AL001 Link Adapters, connect the AC hot line to the common terminal of the Link Adapter. A fuse is internally connected to the common line. Cable Lengths Maximum length for RS-232C cable is 15 m.
Page 17
RS-422 and RS-232C Cable Connecting Link Adapter When using a Link Adapter, connect both RS-232C and RS-422 cable straight AL004-(P)E across, as shown in the following diagram. Here the SD terminal of the host com- puter, for example, is connected to the SD terminal of the Link Adapter. See 5-4 Link Adapter AL004-(P)E for the internal configuration of the Link Adapter.
All OMRON PCF and the PF10l APF (length: 1 m) cables come with con- nectors attached. Connectors for all other APF cables must be assembled by the customer.
Crystal Optical Fiber Cable (AGF) Crystal Optical Fiber Cable (AGF) Link Adapters AL005-(P)E and AL006-(P)E can be connected with crystal opti- cal fiber cable in accordance with the following specifications: The transmission distance between Link Adapters AL005-(P)E and AL006-(P)E is basically determined by the difference between the transmitting and receiving levels of the Link Adapters and by the transmission loss over the crystal optical fiber cable.
Backup Power Supply When total transmission loss from the system is subtracted from the transmit/re- ceive differential of the Link Adapters, the margin must be at least 4 dB. To deter- mine total transmission loss, first calculate the loss over the cable by multiplying the loss/km by the total length of the cable.
Page 21
Section Backup Power Supply The following diagram illustrates a situation in which a 12V battery is used as a backup power supply, connected to the Link Adapter in Plant B. If there were no backup power supply in this case, then a power failure in Plant B would cut off signal transmission between Plant A and Plant C.
Link Adapter Repeater Input Link Adapter Repeater Input Link Adapters AL002-(P)E and AL006-(P)E have repeater input terminals. They are used when it is necessary to be sure that power has already been turned on in a system connected to a branch line of the Link Adapter before signals are transmitted along the main line.
Page 24
Repeater Units Repeater Unit RPT01-(P) must be used when the number of Optical Slave Racks, Optical Transmitting I/O Units, I/O Link Units, and Link Adapters con- nected in series exceeds 32. Insert a Repeater Unit between the 32nd and 33rd Units.
Page 25
Section Repeater Units Connections Dimensions...
Various system configurations call for the use of particular Link Adapters. This section presents a number of examples which illustrate the usage of Link Adapters in PC Link Systems, Host Link Systems, Optical Remote I/O Systems, and Wired Re- mote I/O Systems. See 1-4 General Specifications for details on the functions and specifications of particular Link Adapters. PC Link Systems .
Optical links connect only Link Adapters; they do not directly connect to the PC Link Units themselves. In the diagram below, the straight lines represent wire cables and the jagged lines represent optical fiber cables. C-Series PC with Link Adapter PC Link Unit...
(10 m max.) CPU Rack with Host Link Unit Example 2 Optical Host Link Systems can be connected in series using Link Adapter AL004-(P)E as shown below. Optical fiber (APF/PCF) C-Series PC with Optical Host Link Unit RS-422 Link Adapter Link Adapter...
Link Adapter, signals are still transmitted to the other Host Link Units. Host computer RS-422 or RS-232C Link Adapter AL004-(P)E Optical fiber (APF/PCF) Link Adapter AL002-(P)E C-Series PC C-Series PC with with Optical Host Optical Host Link Unit Link Unit Optical Remote I/O Systems Example 1 Example 1: In an Optical System, Units can be connected in series.
Page 30
Optical Remote I/O Systems Example 2 An Optical System with Optical Transmitting I/O Units can be connected with crystal optical fiber cable (AGF) by using Link Adapter AL005-(P)E as shown be- low: Link Adapter AL005-(P)E CPU Rack with Optical Master Optical fiber (APF/PCF) Example 3 An Optical System with an I/O Link Unit can be connected with crystal optical...
Wired Remote I/O Systems Wired Remote I/O Systems Wired Remote I/O Master Units, Remote I/O Slave Units, and Remote Terminals can be directly connected with RS-485 cable, which has a maximum transmis- sion distance of 200 m. In order to extend the transmission distance and/or to reduce noise interference, a pair of AL007-P Link Adapters can be used to insert an optical link between any two Remote I/O Units/Remote Terminals.
Section Link Adapter AL002-(P)E Link Adapter AL002-(P)E The Link Adapter can run on either 100/200 VAC or 12-24 VAC/DC. The repeater input terminals should be shorted across when not being used. For details on the usage of the repeater input, refer to 2-6 Link Adapter Repeater Input . For backup power supplies, see 2-5 Backup Power Supply .
Link Adapter AL004-(P)E Link Adapter AL004-(P)E Switch Settings CTS Selector Set to 0 V to have the clear-to-send (CTS) signal always ON. Set to external to receive an external CTS signal. Termination Resistance When set to ON, connects the built-in termination resistance (220 ); when set to OFF, disconnects it.
Section Link Adapter AL005-(P)E Link Adapter AL005-(P)E Use FC connecters for AGF (crystal optical fiber;) cable. AGF connecters have fixed positions for reception and transmission, so be careful to connect them cor- rectly. The Link Adapter can operate on either 100/200 VAC or 12-24 VAC/DC. For de- tails on auxiliary power supplies, see 2-5 Backup Power Supply .
Link Adapter AL006-(P)E Link Adapter AL006-(P)E Use FC connecters for AGF cable. AGF connecters have fixed positions for re- ception and transmission, so be careful to connect them correctly. This Link Adapter can operate on either 100/200 VAC or 12-24 VAC/DC. The repeater input terminals should be shorted across when not being used.
Section Link Adapter AL007-P Link Adapter AL007-P The AL007-P is used exclusively for Wired Remote I/O Systems. It cannot be used in Optical Remote I/O Systems, nor can it be used in combination with an AL002-(P)E.
Note Optical fiber cable is not easily connected. Figure in extra length when determining cable lengths for making connections and extensions. Crystal Optical Fiber Cable Crystal optical fiber cable is not available from OMRON. Order it directly from the manufacturer. (Applicable fiber: GI 50/25; connector: FC) Appendix A...
Page 40
Standard Models Wire Cable We recommend the following cables for RS-422, RS-232C, and RS-485 connections. Cable type Recommended Cable RS-232C CO-DS-IREVV-SX-10P x 0.18 mm2 (Hitachi Cable) RS-422 CO-HC-ESV-3P x 7/0.2 (Hirakawa Cable) RS-485 VCTF 0.75 x 2C (JIS) Appendix A...
A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. W123-E1-3 The following table outlines the changes made to the manual during each revision. Page numbers refer to previous version. Revision code Date 1990...
Page 43
Authorized Distributor: Cat. No. W123-E1-3 Note: Specifications subject to change without notice. Printed in Japan...