Forced Set/Reset Cancel; Forced Status Read - Omron SYSMAC LINK C1000H-SLK21-V1 System Manual

Table of Contents

Advertisement

CV-mode Commands for PCs

6-5-18 FORCED SET/RESET CANCEL

Command Block
Response Block

6-5-19 FORCED STATUS READ

Command Block
Response Block
23
0A
Command
code
Parameters
102
Memory Areas
The bits (flags) in the following memory areas can be forced set/reset or
released (refer to 6-4 Memory Area Designations for memory area designa-
tions):
Memory area
IR, SR, LR, HR, and AR
Timer/Counter
Only the number of bits/flags indicated in No. of bits/flags will be forced set/reset
or released.
Cancels all bits (flags) that have been forced ON or forced OFF.
23
02
Command
code
23
02
Command
Response
code
code
Reads the forced status of a specified number of consecutive memory area
words or Timer/Counter Completion Flags starting from the specified word or
flag. All words must be in the same memory area (here, all memory areas with
the same memory area code are considered as one area). This command can
be used with the C200H, C200HS, C200HX, C200HG, and C200HE PCs only.
23
0A
Command
code
Memory area code
Response
First
code
word/flag
Memory area code
Memory area code (command and response): The data area to read forced
status.
First word/flag (command and response): The address of the first word or
flag whose forced status will be read.
Data
Bit status
Completion Flag status
First
No. of items
word/flag
No. of items
Section 6-5
Memory area
Bytes/
code
00
1
01
1
Data
item

Hide quick links: