7) 03- 00~03- 04=【12】Main/ Alternative run source select.
When an input terminal is set to function【12】and is turned on, the run command source is
according to parameter 00-03(Alternative Run source).If the Input is off it will be according to 00-02
( Main run source).
8) 03- 00~03- 04=【13】Main/ Alternative Frequency source Select
When an input terminal is set to function【13】and is turned on, the frequency source is according
to parameter 00-06(Alternative Frequency source).If the Input is off it will be according to 00-05
( Main Frequency source).
9) 03- 00~03- 04=【14】Rapid Stop (controlled deceleration stop)
When DI is on, motor decelerates to stop.
When turning off DI (remove ES), BDI50 won't run again. BDI50 runs again only after giving Run
command again.
10) 03- 00~03- 04=【15】Base Block (Coast to stop)
When DI is on, motor free runs to stop.
When turning off DI (remove BB), BDI50 will start running from 5Hz below the set frequency, to 5Hz
above the set frequency, and then back to the set frequency.
11) 03- 00~03- 04=【16】Disable PID Function.
When an input terminal is set to function【16】and is turned on, PID functions is disabled, if it is
turned off , PID function is enabled again.
12) 03- 00~03- 04=【17】Reset
When a failure that can be manually reset occurs, turn on a terminal with function 【17】, the failure
will be reset. (Same function as the Reset button on keypad).
13) 03- 00~03- 04=【18】Auto _ Run Mode
When an input terminal is set to function【18】, the programmable auto- sequencer function is
enabled, Refer to description of parameter group 6.