Download Print this page

gefran BDI50 Series User Manual page 103

Compact v/f & sensorless inverter

Advertisement

Auto RUN (Auto Sequencer) examples are shown in the following pages:
Example 1. Single Cycle (06- 00=1,4)
The inverter will run for a single full cycle based on the specified number of sequences, then it
will stop. In this example 4 sequences are set, three in forward direction and one in Reverse.
Auto Run Mode.
06- 00=【1】or【4】,
Frequency
05- 01=【15】Hz, 06- 01=【30】Hz, 06- 02=【50】Hz, 06- 03=【20】Hz
Sequence Run Time 06-16=【20】s, 06-17 =【25】s, 06-18=【30】s, 06-19=【40】s,
Direction
(REV)
Unused Sequence Parameters 06-04~ 06-07=【0】Hz , 06-20~06-23=【0】s , 06-36~06-39=
【0】
Hz
RUN command
S1 to S5 auto
run enable
06-32=【1】FWD, 06-33 =【1】FWD, 06-34=【1】(FWD), 06-35=【2】
06-02
06-01
05-01
06-17
06-16
06-03
06-18
RUN
ON
4-56
T
06-19

Hide quick links:

Advertisement

loading