gefran BDI50 Series User Manual page 119

Compact v/f & sensorless inverter

Advertisement

10- 03 =【2】
Feedback (detected value) is derivative controlled in unit time set in parameter 10- 07.
10- 03 =【3】
Ddeviation (target value - detected value) is derivative controlled in unit time set in parameter
10- 07. If the deviation is positive, the output frequency decreases, vice versa.
10- 03 =【4】
Feed back (detected value) is derivative controlled in unit time set in parameter 10- 07.
If the deviation is positive, the output frequency decreases, vice versa.
Note:
For 10-03 = 1 or 2, If the deviation is positive, the output frequency increases and, vice
versa.
For 10-03 = 3 or 4, If the deviation is positive, the output frequency decreases, vice versa.
When 10-03= 【5~8】, Output frequency = PID output frequency + frequency command (10-
03 = 【1~4】) .
Feedback Gain coefficient
10- 04
【0.00 ~ 10.00】
Range
10-04 is the calibration gain. Deviation = set point – (feedback signal×10-04)
10- 05
Proportional Gain
【0.0 ~ 10.0】
Range
10- 05: Proportion gain for P control.
Integral Time
10- 06
【0.0 ~ 100.0】s
Range
10- 06: Integration time for I control
Derivative Time
10- 07
【0.00 ~ 10.00】s
Range
10- 07: Differential time for D control
PID Offset
10- 08
【0】: Positive Direction
Range
【1】: Negative Direction
PID Offset Adjust
10- 09
【0 ~ 109】%
Range
10- 08 /10- 09: Calculated PID output is offset by 10-09 (the polarity of offset is according
to10-08)
PID Output Lag Filter Time
10-10
【0.0 ~ 2.5】s
Range
10-10: Update time for output frequency.
10-11
Feedback Loss Detection Mode
【0】: Disable
Range
4-72