Actual acceleration time=
Actual deceleration time=
V/F Maximum output
Frequency or motor rated
frequency
The minimum starting
frequency
V/F Maximum output frequency is for VF curve, which can be checked from table when VF curve is
fixed. Maximum output frequency is 01-02 when VF curve is customized, or motor rated frequency
02-06
00-18
Jog Frequency
【1.00~25.00】Hz
Range
00-19
Jog Acceleration Time
【0.1~25.5】s
Range
Jog Deceleration Time
00-20
【0.1~25.5】s
Range
The JOG function is operational by using the multi-function input terminals S1 to S5 and setting
the relevant parameters 03-00~03-04 to 【6】JOG FWD or【7】JOG REV. Refer to parameter
group 3.
(00-14)x(set frequency-the minimum starting frequency)
(00-15)x(set frequency-the minimum starting frequency)
Hz
Set frequency
0
Actual acc-time
Acc-time 00-14
Motor rated frequency
Motor rated frequency
Actual dec-time
Dec-time 00-15
4-28