Additional protective
functions
Environment
Protection degree
Specification
Operating temperature
Storage temperature
Humidity
Altitude
Vibration
Communication Function
Braking unit
EMC filter
Certification
CE
RoHS
cULus
Heatsink over temperature protection, Auto carrier frequency
reduction with temperature rise, Protection of reverse
operation, Auto restart attempts setting, Parameter lock
IP20
-10~ +40°C (size 1), -10~+50°C (all other sizes)
-20~60°C
Under 95%RH ( no condensation)
1000 meters or lower
Under 20Hz, 1G(9.8m/s²); 20~50Hz 0.6G(5.88m/s²)
Built in: RS-485 with Modbus RTU / ASCII (standard RJ45
connection), BACnet
Optionals: Profibus, DeviceNet, CANopen, TCP/IP
Built-in on 3ph 400V Class and 3ph 200V Class from 3.7kW to
7.5kW
Built-in on –F version 1ph 200V Class and 3ph 400V Class
In compliance with EN61800-3 (CE & RE) and EN61800-5-1
(LVD)
Note: Inverter can get the better grounding effect with grounding kit.
Conformity to RoHS directive
UL508C