Auxiliary Power For Accessories; Recloser Interface (Rif) Module Configuration - Cooper Kyle Form 5/Triple-Single Installation Instructions Manual

Microprocessor-based recloser control
Table of Contents

Advertisement

SAFETY
FOR LIFE
AUXILIARY POWER FOR
ACCESSORIES
Connection P9 (Figure 20) on the Power Supply module
provides 28Vdc (12Vdc is available) to power radio com-
munication units, RTUs and other accessories. The auxil-
iary power provides 40W peak load capability. Auxiliary
power is fused at 1 Amp (F1) and current-limited to pre-
vent user loads from disabling the control.
Customer 28V connections for auxiliary power are made
to terminals 3 and 1 and are continuously energized. Ter-
minal 2 and 4 are not used at this time.
MANUAL
BATTERY
RECONNECT
P
O
W
E
R
F1
S
GDC-1A
U
P
SW (-) 4
P
28V (-) 3
L
SW (+) 2
28V (+) 1
Y
Figure 20.
Power Supply Module Connection P9 provides
28Vdc power to radio communication units.
P
8
C
P
U
P
9
A
U
X
RECLOSER INTERFACE (RIF)
MODULE CONFIGURATION
CAUTION: Equipment damage. Always wear a ground-
ing wrist strap to control static electricity before handling
circuit boards. Failure to use this strap may result in cir-
cuit board damage.
The Recloser Interface (RIF) Module accepts either 12,
120, or 240 Vac voltage inputs for metering. The RIF Mod-
ule is factory-configured at 120 Vac. The available volt-
ages and their settings are indicated on the operator
panel of the RIF module. Two sets of dip switches, located
on the RIF operator panel, utilize different switch positions
to configure the desired voltage. See Figure 21.
Configure the RIF board by positioning the dip switches to
the desired voltage setting.
Reference the voltage table next to the switches. The
ON position is to the left; the OFF position is to the right
(Figure 21).
RECLOSER
INTERFACE
MODULE
VOLTAGE SENSOR
CONFIGURATION
12
120
240
VAC
VAC
VAC
OFF
6 (Z)
ON
OFF
ON
ON
OFF
ON
OFF
OFF
4 (Y)
ON
ON
OFF
ON
OFF
OFF
2 (X)
ON
ON
OFF
5 (C)
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
3 (B)
ON
ON
OFF
ON
OFF
OFF
1 (A)
ON
ON
OFF
PHASE
BUSHING
NUMBER
DIP SWITCH
POSTION
BUSHING
NUMBER
PHASE
Figure 21.

Recloser Interface (RIF) Module configuration.

S280-42-3
T253.1
P
2
P
O
W
E
R
P
3
C
P
U
6
O
5
O
F
N
4
F
3
P
P
2
O
O
7
S
S
1
S
I
I
6
T
T
I
5
I
O
4
O
N
3
N
2
1
P
4
C
P
U
P
8
6 (Z)•
V
O
4 (Y)•
L
T
2 (X)•
A
G
E
5 (C)•
S
E
3 (B)•
N
S
O
1 (A)•
R
S
POLARITY
DOT
21