4 way sounder circuit controller signalgeber-ausgangsmodul modulo 4 uscite supervisionate

Advertisement

Quick Links

CSC354CPR
4 Way Sounder Circuit Controller
Signalgeber-Ausgangsmodul
Modulo 4 uscite supervisionate
www.acornfiresecurity.com
www.acornfiresecurity.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the CSC354CPR and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cooper CSC354CPR

  • Page 1 CSC354CPR 4 Way Sounder Circuit Controller Signalgeber-Ausgangsmodul Modulo 4 uscite supervisionate www.acornfiresecurity.com...
  • Page 2 www.acornfiresecurity.com www.acornfiresecurity.com...
  • Page 3: Table Of Contents

    www.acornfiresecurity.com Contents Contents / Inhalt / Contenuti INSTALLATION / INSTALLATION / INSTALLAZIONE....................4 WIRING SCHEMATIC / ANSCHLUSSPLAN / SCHEMA DI COLLEGAMENTO............5 WIRING NOTES / ANMERKUNGEN / NOTE DI CABLAGGIO..................5 FUNCTIONAL DESCRIPTION / FUNKTIONSBESCHREIBUNG / FUZIONALITÀ.............6-7 COMMISSIONING INSTRUCTIONS / PROGRAMMIERANLEITUNG / PROGRAMMAZIONE......... 8 OPERATING INSTRUCTIONS / BEDIENUNG / ISTRUZIONI OPERATIVE..............
  • Page 4: Installation / Installation / Installazione

    www.acornfiresecurity.com Installation Instructions 1. Installation (a) Remove the front cover by unscrewing the screw at the top of the unit. (b) Pull the top of the front cover towards you. (c) Secure the back box to the wall using the two holes provided.
  • Page 5: Wiring Schematic / Anschlussplan / Schema Di Collegamento

    www.acornfiresecurity.com Installation Instructions 2. Wiring Schematic / Ansschlussplan / Analogue Addressable Loop Schema di collegamento Brandmelderring Loop IN / OUT 230 V AC Mains Netz Alimentazione Sounder Circuits Signalgeberlinien Uscite Supervisionate 2 x 12V / 4.0Ah Back up battery Notstrombatterie Batteria 3.
  • Page 6: Functional Description / Funktionsbeschreibung / Fuzionalità

    Operating Instructions 4. Functional Description 4. Funktionsbeschreibung CSC354CPR is a 4-way sounder circuit controller with an Am CSC354CPR stehen 4 überwachte Ansteueraus- internal power supply and battery back-up. The CSC354CPR gänge für konventionelle Signalgeber zur Verfügung, sits on the addressable loop of the CIE and takes one die Leitungsüberwachung erfolgt im Gegenpolprinzip...
  • Page 7 4. Funzionalità Fault Condition Analogue Value Störung Analogwert Il CSC354CPR è un modulo a 4 uscite supervisionate Condizione di Guasto Valore Analogico con all’interno un alimentatore supplementare e batterie tampone. Il CSC354CPR è collegato sulla linea indirizzata Sounder Circuit 1 Fault...
  • Page 8: Commissioning Instructions / Programmieranleitung / Programmazione

    www.acornfiresecurity.com Operating Instructions 5. Commissioning Instructions 6. Operating Instructions The cause and effect rules to be applied the sounder There are no confi gurable parts on the sounder controller, circuits must be programmed into the CIE using the “Site all cause and effect must be done at the CIE using the Site Installer”...
  • Page 9: Technical Specification / Technische Daten / Specifiche Tecniche

    www.acornfiresecurity.com Technical Specifi cations 8. Technical Specifi cation / Technische Daten / Specifi che Tecniche PSU Specifi cation Minimum Nominal Maximum Energieversorgung Specifi che Alimentatore Minimo Nominale Massimo Mains Supply Voltage Netzspannung 230VAC +10%, -15% Tensione di Alimentazione Mains Current Consumption Netzstromaufnahme 40mA 500mA...
  • Page 10 www.acornfiresecurity.com Technical Specifi cations 8. Technical Specifi cation / Technische Daten / Specifi che Tecniche Battery Specifi cation Minimum Nominal Maximum Akku Specifi che Batteria Minimo Nominale Massimo Number of Batteries Anzahl Batterien Numero di batterie Manufacturer Hersteller YUASA NP4-12 Produttore Voltage / Spannung / Tensione Capacity / Kapazität / Capacità...
  • Page 11 www.acornfiresecurity.com Technical Specifi cations 8. Technical Specifi cation / Technische Daten / Specifi che Tecniche Loop Specifi cation Minimum Nominal Maximum Loop Specifi che del Loop Minimo Nominale Massimo Operating Voltage (Vmin & Vmax) Betriebsspannung 18.5V Tensione di funzionamento Quiescent Current / Ruhestrom / Corrente a riposo 310µA Alarm Current / Alarmstrom / Corrente in allarme Addressing Mode...
  • Page 12 www.acornfiresecurity.com Technical Specifi cations 8. Technical Specifi cation / Technische Daten / Specifi che Tecniche Short Circuit Isolator Specifi cation Minimum Nominal Maximum Kutzschlußisolator Specifi che Isolatore Corto Circuito Minimo Nominale Massimo Total Loop Resistance for correct operation of short circuit isolator Leitungswiderstand 50Ω...
  • Page 13 www.acornfiresecurity.com Technical Specifi cations 8. Technical Specifi cation / Technische Daten / Specifi che Tecniche Short Circuit Isolator Specifi cation Minimum Nominal Maximum Kutzschlußisolator Specifi che Isolatore Corto Circuito Minimo Nominale Massimo Output Voltage Ausgangsspannung 18.5V Tensione di uscita Loading Per Circuit Ausgangstrom pro Ausgang 800mA Carico per uscita...
  • Page 14 www.acornfiresecurity.com Technical Specifi cations 8. Technical Specifi cation / Technische Daten / Specifi che Tecniche Mechanical Specifi cation Minimum Nominal Maximum Abmessungen Specifi che meccaniche Minimo Nominale Massimo Material PC / ABS / Steel Materiale Dimensions (w / h / d) Abmessungen (B/H/T) 300mm x 300mm x 74mm Dimensioni (L x H x P)
  • Page 15 Technical Specifi cations CSC354CPR Input / Output device and integrated Power Supply for use in fi re detection and fi re alarm systems for buildings. Ein-/Ausgangsmodul mit Kurzschlußisolator und integrierter Spannungsversorgung 0051 Modulo ingresso/uscita con isolatore di corto circuito e alimentatore integrato...
  • Page 16 www.acornfiresecurity.com www.acornfiresecurity.com...