Manual Capacity Control - Danfoss ADAP-KOOL AK-HP 780 Design Manual

Heat pump controller with oil management, refrigeration control systems
Table of Contents

Advertisement

Manual capacity control

1. Go to overview
2. Select suction group
Press the suction group button for the suction group that is to
be controlled manually.
Press the +-button to go on to the next page
3. Set capacity control to manual
4. Set capacity in percent
Press in the blue field against Manual capacity.
AK-HP 780
Heat pump controller
RS8GF202 © Danfoss 2015-08
If you need to manually adjust the capacity of the compressors, you can
use the following procedure:
WARNING!
If you force control the compressors, the oil management will be shut
down. This could cause compressor damages.
(If the wiring of the compressors includes safety relays, monitoring will
continue. See Regulating functions.)
Press the blue field against Control mode
Select MAN.
Press OK.
Set the capacity to the required percentage.
Press OK.
75