Point
At the top the
signal input is
the left of the
two terminals.
At the bottom
the signal input
is the right of the
two terminals.
S
Pt 1000 ohm/0°C
P
AKS 32R
3: Brown
2: Blue
1: Black
AKS 32
3: Brown
2: Black
1: Red
U
On/Off
AK-HP 780
Signal
Signal
type
Sctrl
S7
Pt 1000
Saux1
Saux2
SS
Sd
AKS 32R /
AKS 2050
P0
-1 - xx bar
Pd
Prec.
AKS 32
-1 - zz bar
0 - 5 V
...
0 - 10 V
Active at:
Ext.
Main
Closed
switch
/
Day/
Open
Night
Level
switch
Heat pump controller
Point
1
2
3
4
Type
AI1
AI2
AI3
AI4
Point
5
6
7
Type
AI5
AI6
AI7
Signal
Module
RS8GF202 © Danfoss 2015-08
9:
Terminal
10:
Terminal
15:
Terminal
16:
Terminal
Terminal
11, 12, 13, 14:
(Cable screen)
8
AI8
Point
Terminal
1 (AI 1)
1 - 2
2 (AI 2)
3 - 4
3 (AI 3)
5 - 6
4 (AI 4)
7 - 8
5 (AI 5)
17 - 18
6 (AI 6)
19 - 20
7 (AI 7)
21 - 22
8 (AI 8)
23 - 24
12 V
5 V
5 V
12 V
Signal type /
Active at
15
Need help?