To Wire The Truvu™ Et Display - Carrier MPC Open XP Series Installation And Startup Manual

Table of Contents

Advertisement

Installing the MPC Open XP
3
Strip about 0.25 inch (0.6 cm) of the inner insulation from each wire.
4
Wire the MPC Open XP's Rnet+ and Rnet- terminals to the terminals of the same name on the Equipment
Touch's connector.
NOTES
If using shielded wire, connect the shield wire and the ground wire to the Gnd terminal.
Verify that the Enhanced Access DIP switch is set to Off.
5
Turn on the MPC Open XP's power.
6
Turn on the Equipment Touch.
To wire the TruVu™ ET Display
WARNING Do not apply line voltage (main) - 24 Vdc power only.
Wiring power
Wire the TruVu™ ET Display 24V DC connector to the 24 Vdc power supply using 2-conductor 18 AWG wire.
Maximum distance 100 feet (30 meters).
CAUTION The TruVu™ ET Display can share a power supply with the Carrier controller as long as:
The power supply is DC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
NOTE Purchase a power supply from a third-party manufacturer.
MPC Open XP
MPC Open XPIO48/816
Installation and Start-up Guide
24
CARRIER CORPORATION ©2019
All rights reserved