MSA Ultima X Series Installation & Maintenance Instructions Manual page 39

Gas monitors
Hide thumbs Also See for Ultima X Series:
Table of Contents

Advertisement

OPERATION
LEDs
GREEN RED
NORMAL
ON
OFF
steady
ALARMING
OFF
Flashing
FAULT
OFF
ON
steady
POWER
OFF
ON
UP (HART
steady
Version)
POWER
OFF
ON
UP
steady
(Non-HART
Version)
COUNT
OFF
ON steady ALERT option
DOWN (All
Versions)
SENSOR
OFF
ON steady 3.0 mA if Swap Delay
MISSING/
COUNT-
DOWN
SENSOR
OFF
ON steady 3.75 mA if cal signal
CAL
CAL
OFF
ON steady 4 mA if 4 mA calibration
4-20
CAL FAULT
OFF
ON steady Gas value
UNDER-
OFF
ON steady 3.0 mA if gas value
RANGE
OVER-
ON
OFF
RANGE/
steady
4
LOC
4 to 20 mA
Gas value
Gas value
3.0 mA
<3.75 mA
<3.1 mA
1
disabled;
21.0 mA for O 2 ;
3.75 mA for others
ALERT option
1
enabled:
3.75 mA for all
timeout
2
expired,
Swap Delay
3
disabled
or FAULT
Previous gas value
3
if Swap Delay
enabled
and Swap Delay timeout
not expired
enabled and ALERT
option
1
enabled;
gas value if cal signal
disabled
21.0 mA for O 2 if
cal signal enabled and
ALERT option
1
disabled
selected
20 mA if 20 mA
calibration selected
0 or less;
gas value otherwise
4
21.0 mA
FAULT RELAY
Energized
Energized
De-energized
De-energized
De-energized
Energized
if ALERT option disabled
De-energized
if ALERT option enabled
3
De-energized if Swap Delay
timeout
2
expired, Swap
Delay
3
disabled or FAULT
Energized if Swap Delay
enabled and Swap Delay
2
timeout
2
not expired
Energized if ALERT
option disabled
De-energized if ALERT
1
option enabled
Energized if ALERT option
disabled
De-energized if ALERT
1
option enabled
De-energized two seconds
every minute
De-energized
Energized
2-3
3