Default Configuration
Table D-16. Default Configuration
PARAMETER
Lower Range Value
Upper Range Value
PV Units
Sensor type
Number of wires
Damping time constant
Fault-indication jumper
Write-protect mode
Number of response preambles
Alarms
Calibration Using a HART
Sensor Zero Selection Menu
Select Sensor Calibration from the "Sensor Trim" Menu
Sensor calibration or "trim" functions are available from several
locations in the menu structure. See FIGURE D-8 for a view of this
selection menu.
First warning screen
Once the sensor calibration feature is selected, a warning message
displays to indicate that the 4-20 mA output should be disabled from
any automatic control loop to prevent false action during calibration.
The user must acknowledge this screen to continue. See FIGURE D-9
for a view of this warning screen. Optionally, the user may abort the
process at this screen.
Second warning screen
After acknowledgement of the control loop message, a second warning
message displays, informing the user that sensor calibration will be
changed. The user can abort the procedure at this time or acknowledge
the screen to proceed. See FIGURE D-10 for a view of this screen.
Zero Sensor function select screen
Upon acknowledgement of the calibration change warning screen, a
calibration function selection screen appears. To zero the sensor, select
DEFAULT VALUE
0
Sensor dependent
Sensor dependent
various
3
N/A
Sensor dependent
write enabled
5
Enabled
®
Communicator
D-35