Ultima X Series Gas Monitor Internal Relays; Relay Specifications; Table A-2. Relay Specifications - MSA Ultima X Series Installation & Maintenance Instructions Manual

Gas monitors
Hide thumbs Also See for Ultima X Series:
Table of Contents

Advertisement

NOTE: To avoid electrical noise problems, do not run AC lines from
relays in the same conduit or cable tray as the DC Signal lines.
See Ultima Controller and Calibrator Manual (P/N 813379) for complete
relay configuration information.
Power cable wiring lengths for the Ultima X Series Gas Monitor with
internal relays differ from models without internal relays (TABLE A-1).
Table A-1. Cable Length and Wire Size for Units
With Internal Relays
GAS
SENSOR
DC
TYPE
OUTPUT
VOLTAGE
SUPPLY
Oxygen
or Toxic
3 Wire
12 VDC
24 VDC
Combustible
3 Wire
12 VDC
24 VDC
XIR
3 wire
12 VDC
24 VDC
In all installations, twisted instrument-quality cable is
recommended.
Shielded cable is recommended in situations where radio
frequency interference (RFI), electro-magnetic interference (EMI)
or other electrical noise sources exist or are anticipated.

Ultima X Series Gas Monitor Internal Relays

Relay Specifications

Table A-2. Relay Specifications

TEMPERATURE
RANGE
HUMIDITY
RELAYS
3 ALARMS SPDT FAULT
(NORMALLY-ENERGIZED)
RELAY
At 125 or 250 VOLTS AC,
RATINGS
NON-INDUCTIVE
At 30 Volts DC,
NON-INDUCTIVE
A-2
WIRE
MAXIMUM
SIZE
CABLE LENGTH
(AWG)
WITHOUT HART
(FEET)
(METERS)
16
2,500
762
16
8,000
2,438
16
900
274
16
3,000
914
16
400
152
16
2,500
762
-40 to +60°C (-40 to +140°F)
15 to 95% RH, non-condensing
(Single pole, double throw)
SPDT (Single pole, double throw)
5.0 Amps or 5 Amps @ 1/10 Hp
5.0 Amps or 5 Amps @ 1/10 Hp
MAXIMUM
LOAD
RESISTANCE
(OHMS)
250
500
250
500
250
500