Command #188: Write Relay Normal State
This command sets the Ultima X Normal relay state. This is a single
byte containing a bit map of the three alarm relays' non alarm states.
Not all gas sensors have on-board relays.
Request Data Bytes
BYTE
FORMAT
0
Bit 0
0
Bit 1
0
Bit 2
Response Data Bytes
BYTE
FORMAT
0
Bit 0
0
Bit 1
0
Bit 2
Command-Specific Response Codes
CODE
CLASS
0
Success
1-4
5
Error
6
7
Error
8-15
16
Error
17-31
32
Error
33-127
DESCRIPTION
Alarm #1 0 = normally de-energized, 1 = normally energized
Alarm #2 0 = normally de-energized, 1 = normally energized
Alarm #3 0 = normally de-energized, 1 = normally energized
DESCRIPTION
Alarm #1 0 = normally de-energized, 1 = normally energized
Alarm #2 0 = normally de-energized, 1 = normally energized
Alarm #3 0 = normally de-energized, 1 = normally energized
DESCRIPTION
No Command-Specific Errors
Undefined
Too few data bytes
Undefined
In write protect mode
Undefined
Access Restricted
Undefined
Busy
Undefined