Control And Indicating Panel Selection; Alarm Numbers; Table 2: Overview Of Control And Indicating Panel Selection - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

4 Project planning for control and indicating panels
4.1

Control and indicating panel selection

The control and indicating panel size is determined by the number and location of the detec-
tors.
To avoid exceeding maximum line lengths in a loop or spur, we recommend installing a num-
ber of smaller SIGMANET-capable control and indicating panels in large-scale systems
(SIGMASYS C).
Overview of control and indicating panel selection
Max. number of spurs
Max. number of GMG/PMG, MPL
Max. number of loops
Detectors/loop SIGMASYS/FDnet
Detector zones
Objects/areas
Max. number of detectors
SIGMANET
Possible detectors/peripheral elements
SIGMACON MS 6/7/9
SIGMASYS-detectors
(BASE/PLUS/EXPERT/SPACE)
TM
Sinteso
MS8 detector on PMG-S module
Radio sensor via gateway
Zone operating panel
Transponder/contact coupler
Indicator panel control facility

Table 2: Overview of control and indicating panel selection

X = can be installed
1)
observe maximum number of datapoints
2)
SIGMASYS Sinteso
4.1.1

Alarm numbers

The following number ranges can be created to facilitate system operation and organization.
Data input guideline for:
Object:
Area:
Organisational detector zone number: max. 9 characters, digits and spaces
The organisational detector zone numbers are displayed in the case of alarms.
The appropriate OBJ, AZ and ORG numbers must be unique throughout the entire
SIGMANET system.
The decision of numbers by using leading '0' is not allowed.
Operating inputs may be configured only with 4 characters.
10 / 128
SIGMASYS C
8
4
128 / 126
1)
512
8 / 89
1)
512
X
TR
X
2)
X
X
X
8
X
X
TR = via transponder
TM
alarm and indicating panel S24230-C600-A10
max. 9 characters, digits and spaces
max. 9 characters, digits and spaces
SIGMASYS M
48 (6 x 8)
48 (6 x 8 MPL per module)
24
128 / 126
512 (1024)
8 / 89
1700
X
TR/GMG-S
X
X
X
X
8 per MPC max. 32 per control and
indicating panel
X
X
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)

Hide quick links: