4.3

Interface configuration

Security Products
The interfaces TTY, RS485 and RS232 are available for operating the device. To
change the Interface, device must be opened to replug 5 jumpers.
Follow the instructions to change the interface:
Remove the lateral cover
Disconnect the 5 jumpers currently installed
Reconnect the 5 jumpers to the desired interface jumperblock regarding the
labelling
The following illustration shows the configuration for TTY-Inferace usage:
Fig. 1
Jumperblocks for inferfaces:
1
TTY
2
RS232
3
RS485
RS485-Termination:
Next to the RS485 jumper block a single jumper for the RS485 termination is
located. This jumper must be removed when multiple SUT50 in the configuration of
RS485 are connected together to a common interface-cable.
Setting-up for operation
1
2
3
9
UM_SUT50_EN.doc
06.2014