Parameters
Außentemp. Punkt2
(outdoor temp. for point 2)
Vorlauftemp. Punkt2
(flow temp. for point 2)
Absenkdiff. Punkt2
(set-back difference for point 2)
Außentemp. Punkt3
(outdoor temp. for point 3)
Vorlauftemp. Punkt3
(flow temp. for point 3)
Absenkdiff. Punkt3
(set-back difference for point 4)
Außentemp. Punkt4
(outdoor temp. for point 4)
Vorlauftemp. Punkt4
(flow temp. for point 4)
Vorlauftemp. max.
(max. flow temperature)
Vorlauftemp. min.
(min. flow temperature)

5.1.3 Fixed set point control

The flow temperature can be regulated to a fixed set point during the times-of-use. Outside the
times-of-use, this set point is reduced by the amount in Set-back difference.
Note: The outdoor temperature has no effect on the closed-loop control.
2
[Übersicht > Service > Heizkreis 1...3]
This menu can only be selected after the application key number has been entered!
Parameter
Kennlinienart (type of character-
istic) = Festwert (fixed set point)
WE
Adjustment range
–5 °C
–20 to
80 °C
15 °C
5 °C
–20 to
68 °C
20 °C
10 °C
–20 to
50 °C
90 °C
20 °C
WE
Adjustment range
Steigung
Four-point, gradient, fixed set point
Functions of the heating circuit
50 °C
20 to 160 °C
0 to
30 °C
50 °C
20 to 160 °C
0 to
30 °C
50 °C
20 to 160 °C
20 to 120 °C
20 to 120 °C
31
EB 5571-2 EN