X500/X501 Drive-Cliq Interfaces; X520 Bidirectional Digital Inputs/Outputs - Siemens SINAMICS Equipment Manual

Medium-voltage drives, supplementary component descriptions
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

5.1.2.2

X500/X501 DRIVE-CLiQ interfaces

Table 5-2
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
5.1.2.3

X520 bidirectional digital inputs/outputs

Table 5-3
Type: Screw terminal 1
L1+: The 24 V DC infeed for DI/DO 0 to 7 (first potential group) must always be connected if at least
1)
one DI/DO of the potential group is used as an output.
M1: The ground reference for DI/DO 0 to 7 (first potential group) must always be connected if at least
one DI/DO of the potential group is used as an input or output.
DI/DO: Bidirectional digital input/output
Supplementary component descriptions
Manual, 06/2019
X500/X501 DRIVE-CLiQ interfaces
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
X520 digital inputs/outputs
Terminal
1
1
2
3
4
5
6
7
8
9
10
10
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
Designation
Technical data
1)
L1+
See Chapter "Technical data".
DI/DO 0
DI/DO 1
DI/DO 2
DI/DO 3
DI/DO 4
DI/DO 5
DI/DO 6
DI/DO 7
M1 (GND)
Terminal Modules
5.1 Terminal Module TM15
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents