X200-X202 Drive-Cliq Interfaces - Siemens SINAMICS S120 System Manual

High frequency drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

High Frequency Modules
5.3 HF Motor Module
NOTICE
Damage to motor due to incorrectly connected KTY temperature sensor
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats. Overheating can cause damage to the motor.
• Connect the KTY temperature sensor with the correct polarity.
NOTICE
Failure of components as a result of unshielded or incorrectly routed cables to
temperature sensors
Unshielded or incorrectly routed cables to temperature sensors can result in interference being
coupled into the signal processing electronics from the power side. This can result in
significant disturbance of all signals (fault messages) up to failure of individual components
(destruction of the devices).
• Only use shielded cables as temperature sensor cables.
• If temperature sensor cables are routed together with the motor cable, use separately
• Connect the cable shield at both ends to ground potential through a large surface area.
• Recommendation: Use suitable MOTION CONNECT cables.
5.3.2.3

X200-X202 DRIVE-CLiQ interfaces

Table 5-4
X200-X202 DRIVE-CLiQ interfaces
Pin
1
2
3
4
5
6
7
8
A
B
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
46
shielded cables twisted in pairs.
Name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
System Manual, 10/2020, 6SL3097-5AH10-0BP0
High Frequency Drive